Product Introduction



Outdoor integrated cabinet (three compartments)
Directory:
- Product Description
- Product parameters
- Order Information
-
Features:l High reliability, maintenance-free, quick assembly, suitable for harsh outdoor environmentsl High integration, small footprint, short construction period, effectively reducing construction costsl Complete thermal design, efficient energy saving and emission reduction, effectively lowering operating costsl Supports quick assembly and complete installation, suitable for various installation scenarios on mountain tops and rooftopsl Dynamic environment monitoring, comprehensive alarm signal detection, real-time alarm information reportingThe power cabinet is divided into a power compartment and a battery compartment, with power equipment and batteries installed separately.The outdoor integrated cabinet power cabinet adopts a metal column frame structure, with the overall material made of galvanized steel plate + EPS sandwich panel or galvanized steel plate + PEF insulation cotton. The thickness of PEF insulation cotton is 20-40mm.a) The cabinet body does not have components that can be directly disassembled from the outside, affecting safety and use;b) The power cabinet made of galvanized steel plate + EPS sandwich panel has a galvanized steel plate thickness of 1.5mm, the thickness of the inner and outer color steel plates of the sandwich panel is 0.5mm, and the thickness of the EPS sandwich panel is 45mm;c) The power cabinet made of galvanized steel plate + PEF insulation cotton has an outer plate thickness of 1.5mm, an inner plate thickness of 1.0mm, and a thickness of PEF insulation cotton of 20-40mm;d) The power cabinet is equipped with a 19/21 inch adjustable standard rack + battery layer rack; equipped with 4 pairs of L-shaped support bars;e) The height of the power cabinet base is 150-200mm, the base panel is made of hot-dip galvanized steel plate with a thickness of 2.0mm, and protective panels are installed around the base to prevent animal damage.
-
Technical Parameters:
Serial Number
Product Name
Model Specification
Quantity
Unit
Technical Parameters
Remarks
1
Three-compartment Cabinet
3W-HWG-SC-3
1
Units
A.Cabinet External Dimensions:H*W*D 2100*2250*1000mm
B.Cabinet Internal Dimensions:H*W*D 1800*2150*900mm
C.Cabinet Composition: Cabinet Body+Cabinet Door+Base+Top Cover+Rack+Cabinet Lock
D.Cabinet Type: 1Unit3Compartment, Front3Opening Door
E.Cabinet Material:45MMColor Steel Plate+45mmInsulation Cotton
F.Equipment Layer Rack:19Inch Bracket+2Layer Battery Rack+Air Conditioner Outdoor Unit Space;
G.Cabinet Base:200mmHeight,3.0mmThickness
H.Incoming Line Method: Single Compartment Bottom In Bottom Out Φ50*32
Switching Power Supply
1
Units
A、19Inch6UFrame, Fully Equipped200A B、AC Distribution: Single Phase Input, Total Power AC Circuit Breaker (100A*2P); AC Lightning Protection:40KA*2P
C、DC Distribution: Battery;Air Switch100A*2;
Primary Power Down:63A*2、32A×2、16A×2
Secondary Power Down:100A*2、16A×1、10A×2
D、GPR4850DModule:50A/-48VOutputE、Monitoring Module:RS232/LANCommunication Function3Rectifier Module
3
Three-phase Distribution Box
1
Units
Three-phase Input:63A4P*2City Power, Oil Machine Interlock,BLevel Lightning Protection
Output:63A4P*1、63A1P*1、32A1P*1、16A1P*24
Oil Machine Interface
1
Units
63AThree-phase Five-wire System
Technical Parameters:
Configuration
Project
Technical Indicators
Standard Configuration
Product Model
3W-HWG-SC-3-B
Cabinet External Dimensions (HxWxD)
2000x2400x800mm
Cabinet Material
Galvanized Steel Plate+20mmThicknessInsulation Cotton
Insulation Layer Thickness
20mm/40mm(Other thicknesses can be customized)
Maintenance method
Front opening door
Assembly method
Assembly/Complete assembly
Rack size
19Inch+Battery rack / 19Inch+Device layer rack / 21Inch+Battery rack / 21Inch+Device layer rack
Protection level
IP55
Working temperature
-40℃~+55℃
Optional
Compressor air conditioning
AC220VCooling capacity: 300W / 500W / 800W / 1100W / 1500W / 2000W / 2500W
Heat exchanger
DC48VHeat transfer capacity: 80W/K / 130W/K / 150W/K / 200W/K
Switching Power Supply
DC power supply:DC48V60A / DC48V90A / DC48V120A / DC48V150A / DC48V200A
UPSPower supply
UPS: 1KW / 2KW / 3KW / 6KW / 10KW
Distribution unit
AC distribution /DC distribution /AC and DC distribution
Dynamic environment monitoring
1UMonitoring host includes (access control, water immersion, smoke, impact, temperature and humidity, power failure alarm)
Technical Parameters:
Configuration
Project
Technical Indicators
Standard Configuration
Product Model
3W-HWG-SC-3C
Cabinet External Dimensions (HxWxD)
2030x2400x800mm
Cabinet Material
Galvanized Steel Plate+20mmThicknessInsulation Cotton
Insulation Layer Thickness
20mm/40mm(Other thicknesses can be customized)
Maintenance method
Front opening door
Assembly method
Assembly/Complete assembly
Rack size
19Inch+Battery rack / 19Inch+Device layer rack / 21Inch+Battery rack / 21Inch+Device layer rack
Protection level
IP55
Working temperature
-40℃~+55℃
Optional
Compressor air conditioning
AC220VCooling capacity: 300W / 500W / 800W / 1100W / 1500W / 2000W / 2500W
Heat exchanger
DC48VHeat transfer capacity: 80W/K / 130W/K / 150W/K / 200W/K
Switching Power Supply
DC power supply:DC48V60A / DC48V90A / DC48V120A / DC48V150A / DC48V200A
UPSPower supply
UPS: 1KW / 2KW / 3KW / 6KW / 10KW
Distribution unit
AC distribution /DC distribution /AC and DC distribution
Dynamic environment monitoring
1UMonitoring host includes (access control, water immersion, smoke, impact, temperature and humidity, power failure alarm)